7B41 Isolated, Voltage or Current Input

Introduction

7b30-01-1The 7B41 is a single-channel signal conditioning module that interfaces, amplifies and filters unipolar and bipolar voltage inputs and provides a protected precision output of either +1 V to +5 V or 0 V to +10 V. Model 7B41 features a nonlinearity of ±0.02% maximum and an accuracy of ±0.1% maximum (±0.01% typical). To accurately measure low level signals in electrically noisy environments, 1500 V rms of galvanic transformer-based isolation with a common mode rejection (CMR) of 110 dB @ 50/60 Hz and a normal mode rejection (NMR) of 100 dB @ 50/60 Hz are provided. Rated to operate with a nominal +24 V DC supply, Model 7B41 is mix-and-match and hot-swappable with other 7B Series input modules, so it can be inserted or removed from any socket in the same backplane without disturbing system power.

Inside the 7B41 Series Module

The floating differential input of Model 7B41 is fully protected up to 240 V rms line voltage. A one-pole 10 KHz filter preconditions the input signal prior to amplification by a low drift input amplifier. Amplitude modulation is used to implement transformer isolation (1500 V rms input-to-output and power). Isolated front-end circuitry power is supplied by a DC/DC converter. The output section contains a four pole low pass filter (-3 dB @ 10KHz), a buffer amplifier and a power oscillator. The two-pole output filter and subsequent buffer ensures that a low noise, low impedance (<1Ω ) signal is available at the output to drive loads of 2 kΩ minimum.


Input and Output Ranges

 7b40_fbd
 
Figure 1. 7B41 Functional Block Diagram

7b30fcd 
 
Figure 2. 7B41 Input Field Connections


Input Types
Output Options
±5V to ±50 V
+1 V to +5 V
0 V to +10 V


View and Order Models

  Model  Input Range  Output Range 
Order Now
7B41-01-1 0-10mV
1-5V
Order Now
7B41-01-2 0-10mV
0-10V
Order Now
7B41-02-1
0-100mV
1-5V
Order Now
7B41-02-2  +/-5V
0-10V
Order Now
7B41-03-1  +/-10V
1-5V
Order Now
7B41-03-2
0-1V
0-10V
Order Now
7B41-04-1
0-5V
1-5V
Order Now
7B41-04-2
0-5V
0-10V
Order Now
7B41-05-1
0-20V
1-5V
Order Now
7B41-05-2
0-20V
0-10V
Order Now
7B41-06-1
+/-20V
0-10V
Order Now
7B41-07-1  0-50V
1-5V
Order Now
7B41-07-2  0-50V  0-10V
Order Now
 7B41-08-1 +/-50V  1-5V
Order Now
 7B41-08-2  +/-50V 0-10V 











Specifications

7B41 Specifications
(typical @ +23°C ±5°C and Vs = +24 V dc)

 Description
Model 7B41
Range1
Standard Range
+/- 5V to +/- 50V
Custom Range YES
Output Range Options (RL > 2 kΩ)
1-5V or 0-10V (1)
 Accuracy1
Initial @ +25°
0.01% span (0.1% max)
Nonlinearity2 +/-0.02% max
Input Offset vs. Temperature  0.5uV/C
Zero Suppression vs. Temperature  0.002%Vz/C
Span vs. Temperature
±35 ppm/°C
Output Offset vs. Temperature  +/-0.001% span
Input Bias Current +/- 100 pA 
Input Resistance  
Power ON >1M Ohm
Power OFF >1M Ohm
Overload  >1M Ohm
 Output Noise
5 MHz Bandwidth  2mV peak
 10 Hz to 100 kHz Bandwidth
1mV rms
 0.1 Hz to 10 Hz Bandwidth
0.5uV peak
 Bandwidth, -3 dB 10 KHz (2)
Output Rise Time, 10% to 90% Span
40 us (2)
 Common-Mode Voltage (CMV)
 Input-to-Output and Power
1500 V rms continuous 
Common-Mode Rejection (CMR) 
Input-to-Output and Power @ 50/60 Hz
110 dB
Normal Mode Rejection @ 50/60 Hz  100 dB/dec >10 Khz (2)
Input Protection 120 V rms, continuous
±35 V dc, continuous
Input Transient Protection ANSI/IEEE C376.90.1-1989
IEEE-STD 472
IEC 255-4, Class II
Output Resistance < 1 Ohm
Output Voltage/ Current Limit
+/-12V, +/-14mA
 Power Supply
 Voltage, Rated Performance
14-35Vdc
 Current
20mA max
 Sensitivity
+/-0.0001%/%Vs
 Mechanical Dimensions 1.663" x 2.11" x 0.563
(42.24 mm x 53.6 mm x 14.3 mm)
 Weight  60 grams
 Environmental
Temperature Range
  Operating  -40°C to +85°C
  Storage  -40°C to +85°C
Relative Humidity, 24 hours
 0 to 90% @ +60°C noncondensing
ESD Sensitivity
 IEC 801-2, Level 2
RFI Susceptibility  ±0.5% Span error @ 400 MHz, 5 Watt, 3 ft

Warm-up time required to meet specifications is approximately 10 minutes.
1 +/- 5V and +/- 10V output ranges are available as custom configurations.
2 Custom Bandwidths available, Rise and Fall times, NMR frequency will vary accordingly
Specifications subject to change without notice.