Order Example:
- Model: 5B30-Custom
Input Range: -5 mV to +50 mV
Output Range: 0 V to +5 V
|
5B30-Custom (mV Input - 4 Hz Bandwidth)
| ±5 mV to ±500 mV |
Unipolar (0 to +5 V) Bipolar (-5 V to +5 V) Other (Contact Factory) |
4 Hz (Cannot be changed) |
|
| |
Order Example:
- Model: 5B31-Custom
Input Range: -1.5 V to +10 mV
Output Range: 0 V to +5 V
|
5B31-Custom (V Input - 4 Hz Bandwidth)
| ±0.5 V to ±20 V |
Unipolar (0 to +5 V) Bipolar (-5 V to +5 V) Other (Contact Factory) |
4 Hz (Cannot be changed) |
|
| |
Order Example:
- Model: 5B32-Custom
Input Range: 2 mA to 18 mA
Output Range: 0 to +5 V
|
5B32-Custom (mA Input - 4 Hz Bandwidth)
| 0 mA to 20 mA |
Unipolar (0 to +5 V) Bipolar (-5 V to +5 V) Other (Contact Factory) |
4 Hz (Cannot be changed) |
|
| |
Order Example:
- Model: 5B34-Custom
Input Sensor 100 ohm Pt with alpha = 0.00385
Input Range: -120°C to +645°C
Output Range: 0 to +5 V
|
5B34-Custom (RTD Input)
| 100 ohm Pt alpha = 0.00385 |
-200°C to +850°C |
Unipolar (0 V to +5 V) Bipolar (Not Available) Other (Contact Factory) |
| 100 ohm Pt alpha = 0.003916 | -200°C to +850°C |
| 10 ohm Cu alpha = 0.004274 | -100°C to +260°C |
| 120 ohm Ni alpha = 0.00672 |
-80°C to +320°C |
Note: The bandwidth of all 5B34 input modules is fixed at 4 Hz and cannot be changed.
|
| |
Order Example:
- Model: 5B35-Custom*
Input Sensor: 100 ohm Pt with alpha = 0.00385
Input Range: -40°C to +350°C
Output Range: 0 to +5 V
*Order 5B35-C-Custom for Copper (Cu) RTD sensor inputs. Order 5B35-N-Custom for Nickel (Ni) RTD sensor inputs.
|
5B35-Custom, 5B35-C-Custom, 5B35-N-Custom (RTD Input)
| 100 ohm Pt alpha = 0.00385 |
-200°C to +850°C |
Unipolar (0 V to +5 V) Bipolar (Not Available) Other (Contact Factory) |
| 100 ohm Pt alpha = 0.003916 |
-200°C to +850°C |
| 10 ohm Cu alpha = 0.004274 |
-100°C to +260°C |
| 120 ohm Ni alpha = 0.00672 |
-80°C to +320°C |
Note: The bandwidth of all 5B35 input modules is fixed at 4 Hz and cannot be changed.
|
| |
Order Example:
- Model: 5B36-Custom
Input Range: 150 ohms to 9.5 k ohms
Output Range: 0 to +5 V
Order 5B36-N-Custom for Nickel (Ni) RTD sensor inputs.
|
5B36-Custom (Potentiometer/Slide-Wire Input)
| Minimum = 0 ohms |
Minimum = 25 ohms + Low |
Unipolar (0 V to +5 V) Bipolar (Not Available) Other (Contact Factory) |
| Maximum = 150 ohms |
Maximum = 10 k ohms + Low |
Note: The bandwidth of all 5B36 input modules is fixed at 4 Hz and cannot be changed.
|
| |
Order Example:
- Model: 5B37-Custom
Input Sensor: J Thermocouple
Input Range: -250°C to +1200°C
Output Range: 0 to +5 V
Order 5B37-N-Custom for Nickel (Ni) RTD sensor inputs.
|
5B37-Custom (Thermocouple Input)
| J, K, T, E, R, S, B, N, C |
±5 mV to ±100 mV |
Unipolar (0 V to +5 V) Bipolar (Not Available) Other (Contact Factory) |
Note: The bandwidth of all 5B37 input modules is fixed at 4 Hz and cannot be changed.
|
| |
Order Example:
- Model: 5B38-Custom
Bridge Type: Full (4-arm)
Sensitivity: 1.5 mV/V
Output Range: 0 V to +5 V
|
5B38-Custom (Strain Gage/Load Cell Input)
| Full Bridge of Half Bridge |
1 mV/V to 30 mV/V (Range: ±10 mV to ±300 mV) |
Bipolar (-5 V to +5 V) Other (Contact Factory) |
Note: The standard bridge excitation is +10 volts and cannot be changed.
|
| |
Order Example:
- Model: 5B40-Custom
Input Range: -5 mV to +50 mV
Output Range: 0 V to +5 V
|
5B40-Custom (mV Input - 10 kHz Bandwidth)
| ±5 mV to ±500 mV |
Unipolar (0 V to +5 V) Bipolar (-5 V to +5 V) Other (Contact Factory) |
10 kHz (Cannot be changed) |
|
| |
Order Example:
- Model: 5B41-Custom
Input Range: -1.5 V to +10 V
Output Range: -5 V to +5 V
|
5B41-Custom (V Input - 10 kHz Bandwidth)
| ±0.5 V to ±20 V |
Unipolar (0 V to +5 V) Bipolar (-5 V to +5 V) Other (Contact Factory) |
10 kHz (Cannot be changed) |
|
| |
Order Example:
- Model: 5B42-Custom
Input Range: 2 mA to 18 mA
Output Range: +2 V to +10 V
|
5B42-Custom (Loop Powered mA Input)
| 0 mA to 20 mA |
Unipolar (+2 V to +10 V) Bipolar (Not Available) Other (Contact Factory) |
100 Hz (Cannot be changed) |
|
| |
Order Example:
- Model: 5B45-Custom
Input Range: 500 Hz to 18 kHz
Output Range: 0 V to +5 V
|
5B45-Custom (Frequency Input)
Minimum = 0 Hz Maximum = 5 kHz |
Minimum = 500 Hz + Low Maximum = 20 kHz - Low |
Unipolar (0 V to +5 V) Bipolar (-5 V to +5 V) Other (Contact Factory) |
|
| |
Order Example:
- Model: 5B46-Custom
Input Range: 10 kHz to 120 kHz
Output Range: 0 V to +5 V
|
5B46-Custom (Frequency Input)
Minimum = 0 Hz Maximum = 50 kHz |
Minimum = 20 Hz + Low Maximum = 275 kHz - Low |
Unipolar (0 V to +5 V) Bipolar (-5 V to +5 V) Other (Contact Factory) |
|
| |
Order Example:
- Model: 5B47-Custom
Input Sensor: J Thermocouple
Input Range: -250°C to +1200°C
Output Range: 0 V to +5 V
|
5B47-Custom (Thermocouple Input, Linearized Output)
| J, K, T, E, R, S, B |
±5 mV to ±100 mV |
Unipolar (0 V to +5 V) Unipolar (+1 V to +5 V) Bipolar/Other (Not Available) |
|